Shortcut | RU |
---|---|
Format | RU [axis] = [distance]… (9.2m and later, earlier RU X=n) |
Units | millimeter |
Remembered | Using SS Z |
Shortcut | RU |
---|---|
Format | RU [axis] = [distance]… |
Units | millimeter |
Type | Axis-Specific |
Remembered | Using [addr#]SS Z |
This command sets the servo loop error limit before the motors will be disabled. The value n
, is the distance in millimeters that the internal servo target and the actual position can differ before the motor is disabled. Default is 1 to 2 mm. If spurious disable conditions are encountered, increase this number. For more sensitive crash protection, decrease this number. Prior to MS-2000 version 9.2f and TG-1000 version 3.20 a single value applied to all axes (Tiger card-addressed) but afterwards it is axis-specific. Prior to MS-2000 version 9.2m and TG-1000 version 3.20 only integer values were allowed, but afterwards floating point numbers are allowed and reported.
A positive reply of :A is sent back when the command is received correctly.
RU X=5 :A
Sets runaway sensitivity to 5mm on the X axis for 9.2m and later, sets the sensitivity on all axis for 9.2l and earlier.
1RU X=5 :A
Sets runaway sensitivity to 5mm on all axes in card #1 in v3.19 and earlier, would only set the X axis (assuming it's on card #1) on v3.20 and later.